Transformer Project for RAAF Air Force Base Darwin
RAAF air force base at Tindal near Darwin in NT. Transformers 350kva to 2500kva.
RAAF air force base at Tindal near Darwin in NT. Transformers 350kva to 2500kva.
Due to the most recent developments in epoxy cast coil production, cooling has now been enhanced with new cooling duct material design . We even use metal cooling ducts to enhance the convection cooling with a conduction component.
Core structure rectangular, windings copper, cooling ducts in between windings outside the core window. This is a finite element computer calculation using ANSYS simulation computer software. Transformer ratings:Input 415V- output…
Ideal for testing laboratories, allows testing at different voltages and frequencies
Tortech makes a range of Isolation transformers from single phase 240v-240v up to 50kVA and 3 phase 415v-415v up to 250kVA. Also isolation transformers for medical & RCD testing purposes.
This is one convenient type of discharge reference source for Partial Discharge applications. It can be used to cross check electrical calibrators for partial discharge.
30kVA single phase Isolation Transformer for Railway Application 30kVA Transformer for Railway ApplicationMTM SpecificationsPrimary 230vSecondary 230v+_ 2.5% +_ 5% taps on primarystainless steel 316.Outdoor rated IP56
100kVA 3 phase Isolation Transformer for Railway Application 100kVA Transformer for Railway ApplicationMTM SpecificationsPrimary 400vSecondary 400v+_ 2.5% +_ 5% taps on primarystainless steel 316.Outdoor rated IP56
The picture below is a 3-phase 25kVA -415/415V, with taps on the output winding. This 3 phase transformer is built using 3 single phase toroid transformers. A 3 phase transformer…
Assembled and tested on load here at Tortech our single to three phase converters are an ideal cost effective solution to provide 3 phase power from single phase power. Single…
Item 1 – Cast Resin type Isolation Transformer | HV Winding 1 | LV Winding 1 | LV Winding 2 | |
Rated power | kVA | 315 | 1250 | 1250 |
Rated voltage | kV | 33 | 0.48 | 0.48 |
Frequency | Hz | 50 | ||
Off circuit tapping links | % | ±2.5%, +-5% | Nil | Nil |
Connection | Delta | Star | Star | |
Vector group | Dy11y11 | |||
Insulation level (Maximum BIL/AC) | kV | 150/70 | 10/3 | 10/3 |
Winding material | Aluminium cast windings in quartz filled self-extinguishing epoxy resin | Aluminium cast windings in quartz filled self-extinguishing epoxy resin | Aluminium cast windings in quartz filled self-extinguishing epoxy resin | |
Type of winding | Vacuum Resin Cast | Vacuum Resin cast | Vacuum Resin cast | |
Standard | AS 60076-11, AS 2374 | |||
Installation | Indoor | |||
Degree of protection | IP22 | |||
Type of cooling | AN/AF | |||
Installation altitude | < 1000 a.m.s.l | |||
Climatic/environmental And fire behaviour class | E2-C2-F1 |