An urban transit rectifier 3 phase transformer is used to supply the overhead 1500V DC power to the Sydney and Melbourne Metro railway system. Now prepared in epoxy resin construction, they are maintenance free.

Tortech’s rectifier transformers have high reliability and strong harmonic suppression and good DC voltage balance performance. Using 12 pulse and 24 pulse phase shifting technology the harmonic content is greatly reduced, reaching the latest level of current rail transit technology.

Close Menu
×

Cart

COVID-19 Announcement

Customers and couriers must wait outside the premises now and not come inside. They must call or press bell upon arrival. Staff will bring products out.

Item 1 – Cast Resin type Isolation Transformer

HV Winding 1

LV Winding 1

LV Winding 2

Rated power

kVA

315

1250

1250

Rated voltage

kV

33

0.48

0.48

Frequency

Hz

50

Off circuit tapping links

%

±2.5%, +-5%

Nil

Nil

Connection

Delta

Star

Star

Vector group

Dy11y11

Insulation level (Maximum BIL/AC)

kV

150/70

10/3

10/3

Winding material

Aluminium cast windings in quartz filled self-extinguishing epoxy resin

Aluminium cast windings in quartz filled self-extinguishing epoxy resin

Aluminium cast windings in quartz filled self-extinguishing epoxy resin

Type of winding

Vacuum Resin Cast

Vacuum Resin cast

Vacuum Resin cast

Standard

AS 60076-11, AS 2374

Installation

Indoor

Degree of protection

IP22

Type of cooling

AN/AF

Installation altitude

< 1000 a.m.s.l

Climatic/environmental

And fire behaviour class

E2-C2-F1

test